After cooler ,air copressor cooler,air cooler

After cooler ,air copressor cooler,air cooler
Product Detailed
After cooler compact structure+easy to operate and install for areas: high temperature+humidity+heavy dust CE certificate

After cooler ,air copressor cooler,air cooler  (Water cooled or wind cooled )

HX-W series water cooled high efficiency cooler

1.After cooler brife introduction

1This series chilling after-cooler uses water as the medium cooling down,carrries on the procooling to the high temperature compressed air
2Liminate large amount of moisture content,greasy dirt
3Enable the high temperature compressd air effectively cooled to the fixed temperature
4Ensure the follow-up purification equipment works
5Essential supplementary equipment of the air compressor

2.After cooler working condition

1Design pressure1.0Mpa
2Rated working pressure0.7Mpa
3Allowable working pressure0.4-0.95Mpa(peculiar specification can accept)
4Rated inlet temperature≤120°C
5Rated outlet temperature≤42°C
6Inlet water temperature≤32°C
7Designed temperature difference of inlet&outlet water≤6°C

3.After cooler technical parameter 

Parameter       Model
1 2361012152025
Treatment m³/min1.62.63.87.0 11.513.5 172327
Cooling Power(kw)2.54.0 5.810.817.720.726.1 35.441.5
Cooling water consumption T/H0.40.60.81.52.53.0 3.7 5.15.9
Inlet&outlet caliberRC1"RC1"RC1"RC1-1/2"RC2"RC2"DN65FLDN65FLDN80FL
Cooling water inlet&outlet caliberRC1/2"RC3/4"RC3/4"RC1"RC1"RC1-1/2"RC2"RC2"RC2"
External sizeL135013201350138014501650180018501850
D133159159219219219219245245
Parameter       Model
3040506080100120150170
Treatment m³/min3445556587110130160180
Cooling Power(kw)52.369.284.599.9133.7169.1199.8245.9276.7
Cooling water consumption T/H7.59.912.114.319.124.228.635.239.6
Inlet&outlet caliberDN80FLDN100FLDN100FLDN100FLDN125FLDN150FLDN150FLDN200FLDN200FL
Cooling water inlet&outlet caliberRC2"RC2"DN65FLDN65FLDN65FLDN80FLDN80FLDN100FLDN100FL
External sizeL210019002000210023002250240023502500
D245325325325377426426480480